Brand Name : SHX
Model Number : SCF500A
Certification : ISO9001:2015, CE, TUV, BV
Place of Origin : Foshan, China
MOQ : 1 Set
Price : Negotiation
Payment Terms : L/C, T/T
Supply Ability : 80 Sets per month
Delivery Time : 20 working days
Packaging Details : Standard export packing
Product Name : 500KVA Cummins Genset
Color : Green
Cooling type : Water cooled
Aspiration : Turbocharged and intercooled
Starting method : Electrical start by 24V batteries
Engine brand : Cummins
Alternator brand : Faraday
Control Panel : Smartgen HGM6110N
Green Color Cummins Diesel Generator KTA19-G4 400KW / 500KVA
Genset Specifications:
| Genset model | SCF500A |
| Genset rated power | 400KW / 500KVA |
| Rated voltage | 400/230V (adjustable) |
| Rated current | 720 Amps |
| Frequency | 50 Hz |
| Power factor | 0.8 Lagging |
| Connecting type | 3 phase 4 wire |
| Cooling system | Closed cycle water-cooled with fan, water tank |
| Overall dimension (L×W×H) mm | 3300×1250×1850 |
| Gross weight (kg) | 4670 |
Engine Specifications:
| Diesel Engine | |
| Brand | CUMMINS |
| Model | KTA19-G4 |
| Engine type | 6 cylinders in Line, 4 stroke, direct injection |
| Aspiration | Turbocharged and air-to-air intercooled |
| Rotating speed | 1500 RPM |
| Engine cooling system | Water-cooled |
| Speed governing system | Electronic speed governor |
| Starting method | By 24V batteries |
| Engine filter system | Dry type air filter ,fuel filter, oil filter, water filter |
| Displacement(L) | 19 |
| Bore×Stroke(mm) | 159×159 |
| Compression ratio | 14.5:1 |
| 100% Load fuel consumption (l/h) | ≤96 |
| Lube capacity(L) | 38 |
Alternator Specifications:
| Alternator | |
| Brand | FARADAY |
| Model | FD5M1-4 |
| Excite type | Brushless self-excited AVR regulation |
| Connecting type | 3 phase 4 pole |
| Steady frequency change | 0.50% |
| No load voltage | ≥95%-105% |
| Steady voltage | ≤±1% |
| Insulation class | Class H |
| Protection grade | IP23 |
Manufacturing Standards:
ISO8528; ISO1105; ISO3046; GB/T2820; GB755; BS5000; NEMAMG-22; YD/T502
Electrical Parameters
Wave distortion: <10%
Voltage fluctuation: <0.5%
Voltage / frequency fluctuation: <=0.5%
AVR self-regulated, voltage regulation rate: <=+- 1%
Radio interference restraining accords with stipulation of VDE0875-N and ISO8528
Control Function
Key start / auto start
Monitoring meters: Current; Frequency; Wire Voltage; Genset KVA; Genset KW; Output
Capacity; Output KW.H; Power Factor.
Warning/Shutdown: Alternator Under/Over Volts, Frequency; Under/Over Speed; Low Oil Pressure; High Engine Temp; High/Low Battery Volts; Over Current; Earth Fault Shutdown.
Voltage
Special Type Generator Set
1. Acoustic Enclosure Generator Set.
2. Containerized Generator Set.
3. Trailer-Mounted Generator Set.
4. Mobile Generator Set (Truck Mounted).
|
|
Green Color Cummins Diesel Generator KTA19-G4 400KW / 500 Kva Genset Images |